Home > Electrical
Equipment > Low-voltage equipment Automatic three-phase
circuit breakers A3790
|
A 3790 is a family of automatic circuit breakers that are
designed for operation in networks with an AC voltage of up to 660 V, 50-60 Hz.
They can be used to protect and start asynchronous motors with short-circuited
rotors. - Rated voltage of free contacts
DC 400 V (current 4 A) AC up to
660 V (current 4 A) - Rated voltage of independent release device
DC 110; 220 V AC
440 V - Rated voltage of zero release device
DC 110; 220 V AC 127 ¸
660 V - Rated voltage of electric drive
DC 110; 220 V AC 127 ¸
660 V
Standard construction
| A 3792 |
A 3794 | A 3796 |
A 3798 |
Rated current, A | 630
| Nominal
voltage, V | AC
up to 660 V |
Maximum breaking capacity, kA under the voltage ~380 V, 50 Hz under
the voltage ~660 V, 50 Hz |
50.5 28.6 |
Construction according to the mounting method |
stationary; drawout-type; |
Construction according to the protection type |
current limiting | current
limiting; selective | current
limiting | knife switch |
Construction according
to the maximum-current release device type |
electro- magnetic | electromagnetic;
semiconductor | electromagnetic;
thermal | |
Rated currents of maximum-current
release devices, A | 250;
400; 630 |
Drive type | hand;
remote; electromagnetic |
Construction by type of auxiliary release devices |
independent; zero |
Wear resistance, On/Off cycles
overall switching
|
6000 3000 |
Dimensions, mm | stationary
construction - 225x400x160 drawout construction - 318x400x371.5 |
Volume, dm3
| 14.4 |
Weight, kg |
13.0 ... 33.0 | | |
Search | |
Services offered
to our clients | |
Services offered