    KVTp Model Thermocontracting Terminal Cable Connectors for Indoor Use
    TU36-2674-84 are designed for insulation of cable termination points in cables with aluminium or copper conductors, with plastic or impregnated-paper insulation, in aluminium or plastic sheath, with or without serving. They are for use for alternating voltages of up to 1 kV that are used in circuits with insulated or grounded neutral terminals.
    Thermocontracting terminal connectors TU36-18.34.01-86 are designed for the termination of triple-core or quad-core power cables with voltages ranging from 6 to 10 kV. They are for use in any rooms that meet the requirements of GOST 15150-69.
    The thermocontracting material of which the connector is made is manufactured from thermoplastics using a special technology. After radiation treatment, the material obtains new operating and technological properties, the main one being its capability to contract in volume when warmed up, all the while keeping its initial shape.
    Thermocontracting articles provide complete impermeability and high insulating properties. In addition, they have a high mechanical strength and are resistant to chemical action and environmental effect.
    The thermocontracting terminal connector consists of a thermocontracting glove, the inner surface of which is covered with a hot-melt adhesive, thermocontracting tubes that insulate the terminated cable's conductors, and cable guards. The connector set includes fittings for cold jointing of the earthing cable.

    Notation conventions structure:
    KVTp 3*120-10
     
    "K"
    - terminal
    "V"
    - for indoor use
    "T"
    - thermocontracting
    "p"
    - glove
    "3*120"
    - triple-core cable with the conductor section -120
    "10"
    - voltage (kV)

    Specifications

    Connector typeNumber and section of the cable conductors
    for the rated voltage
    1 kV6 kV10 kV
    3KVTp 1 - 50...253 x 25
    3 x 35
    3 x 50
      
    3KVTp 1 - 120...70
    3KVTp 1 - 240...150
    3 x 70
    3 x 95
    3 x 120
    3 x 150
    3 x 185
    3 x 240
      
    3KVTp 10 - 50...25 3 x 25
    3 x 35
    3 x 50
    3 x 25
    3 x 35
    3 x 50
    3 x 50
    3KVTp 10 - 120...70
    3KVTp 10 - 240...150
     3 x 70
    3 x 95
    3 x 120
    3 x 150
    3 x 185
    3 x 240
    3 x 70
    3 x 95
    3 x 120
    4KVTp 1 - 50...253 x 25 + 1 x 16
    3 x 35 + 1 x 16
    3 x 50 + 1 x 25
      
    4KVTp 1 - 120...70
    4KVTp 1 - 240...150
    3 x 70 + 1 x 25
    3 x 95 + 1 x 35
    3 x 120 + 1 x 35
    3 x 150 + 1 x 50
    3 x 185 + 1 x 70
    3 x 240 + 1 x 85
      

    KVTp model thermocontracting terminal cable connectors for indoor use, drawing
    1 - Glove; 2 - Sleeve joint; 3 - Tube; 4 - Insulating joint.
             
    Search
    Type one or more keywords
     

    Site map
    Services offered to our clients
    Place an order
    Here you can place an order or ask our experts a question.

    E-mail addresses for sales departments:
    machinery department office@mrmz.ru
    electrical equipment department electro@mrmz.ru

    Moscow representative office
    Address and driving directions

    The company
    Address and driving directions
    Services offered to our clients

    Terms of supply

    Rambler's Top100 Rambler's Top100