Home > Electrical
Equipment > Low-voltage equipment Automatic circuit
breakers for DIN-cleat VA6026
|
VA 6026 automatic micro-switches are designed for manual on and
off switching of circuits with voltages of 220/380 V, as well as for the protection
of electric mains and asynchronous motors in emergency state by automatic switch
off. These switches meet the requirements of TU16-90 IGKZh.641252.231TU
SPECIFICATIONS | VA6026 |
Rated current, A |
31.5 | AC 50-60
Hz rated voltage, V | 380/440 |
Release device construction |
combined | Maximum
switching capacity, kA | 3.5 under 220 V, j =
0.8 | Mechanical
wear resistance, On/Off cycles | 20,000 |
Switching wear resistance,
On/Off cycles | 19,000 |
Weight, kg | 0.080
| Operating conditions |
UHL4, 04, T3 | Circuit
breaker protection rate | IP20 |
Mounting | on front
of the board using a latch on standard profiled straps (35 mm wide and 1 mm thick)
with front wire connection |
Number of poles | 1, 2, 3 |
Wire section | 2,5
... 10 mm2 |
| "L"
specification | "G" specification
| "K" specification |
Protection type |
Residential and office building electric main protection |
Manufacturing facilities' electric main protection |
Asynchronous motor protection |
Thermal release device non-operate current / operate current: |
1.05 In / 1.5 In | 1.05 In / 1.35
In | 1.05 In / 1.2 In |
Electromagnetic release device
non-operate current / operate current: | 2.5
In / 10 In | 2.5 In / 10 In |
7 In / 12 In | Release
device's rated current series: | 6.3; 10;
16; 20; 25; 31.5 A | 6.3; 10; 16; 20; 25; 31.5
A | 0.3; 0.5; 0.6; 0.8; 1.0; 1.12; 1.6; 2; 2.5;
3.15; 5; 6.3; 8; 10; 16; 20; 25; 31.5 A | | |
Search | |
Services offered
to our clients | |
Services offered
to our clients | |
|