Home > Electrical
Equipment > Transformers and stabilizers Package
kiosk-type transformer substations
These terminal and double-ended 400 and 630 kilovolt-ampere, 6 (10)
kV transformer substations represent outdoor, single-transformer package substations
that are designed for the intake of three-phase 50 Hz, 6 or 10 kV AC electrical
energy, for its transit (double-ended type substations),for its transformation
to 0.4 kV electric energy and for its supply to consumers in temperate climate
districts (-40°C to +40°C). The transformer substations with an aerial
inlet are connected to the power line by means of a disconnecting switch, which
is installed on the nearest pole.
- Terminal-type transformer substation - KTPT
- Double-ended transformer
substations - KTPP
- Availability
of natural ventilation in the transformer cabinet for the purpose of cooling the
power transformer;
- The RUNN has two-sided maintenance
- A special device
for wheeling the transformer in and out of the cabinet;
- Automatic drawout
circuit breakers are installed on the outgoing lines.
SPECIFICATIONS |
KTP-400 |
KTP-630 |
Transformer type | TMG-400 |
TMG-630 |
Transformer winding connection and group reference |
Y/Yn-0; Δ/Yn-11 |
Transformer rated output, kilovolt-ampere |
400 | 630 |
Rated voltage on the high-voltage side, kV |
6 | 10 | 6 | 10 |
Transformer rated current
on the high-voltage side, A | 38.5 | 23.1 | 60.69 | 36.4 |
High-voltage side fuse interrupting
rating, A | 80 | 50 | 100 | 80 |
Rated voltage on the low-voltage
side, kV | 0.4 |
Transformer rated current
on the low-voltage side, A | 577.4 |
910.4 | Rated
current of the outgoing lines, A | ? 1 |
400 | ?
2 | 200 |
? 3 | 160 |
? 4 |
100 | ?
5 | 100 |
? 6 | - |
400 | ?
7 | - |
250 | ?
8 | - |
160 | Lighting
line | |
Standard construction | with
aerial inlet | with cable inlet | L,
mm | Weight with the transformer, kg | L,
mm | Weight with the transformer, kg |
KTPT-400/10/0.4 | 3150 | 2975 | 4250 | 3700 |
KTPT-630/10/0.4 | 4300 | 4550 | 5480 | 5300 |
Standard construction | L,
mm | Weight with the transformer, kg |
KTPP-400/10/0.4 | 6500 | 5035 |
KTPP-630/10/0.4 | 7720 | 6600 |